We emphasize advancement and introduce new products into the market each year for boiler economizer, Chinese boiler chimney, szs structure boiler, To reward from our strong OEM/ODM capabilities and considerate solutions, remember to speak to us today. We'll sincerely develop and share success with all clientele.
Hot-selling Industrial Electric Boiler - Single Drum Steam Boiler – Double Rings Detail:

Introduction :

Single Drum Chain Grate Coal fired boiler is horizontal three-back water fire pipe composite boiler. Fix fire tube in drum and the light pipe water wall is fixed on the right and left sides of the furnace. With light chain grate stoker for mechanical feeding and by the draft fan and blower for mechanical ventilation, realize mechanical taphole by scraper slag remover.
The hopper of fuel drops to grate bar, then enter furnace for burning, by the ashes room above the back arch, the flame gets through the first backhaul fire tube to front smokebox, then turn back from front smokebox to the second flue for economizer and dust collector, at last, released into the atmosphere by the draft fan through chimney.

dzl dzg Steam Boiler Equipment Layout

Feature:

1. High thermal efficiency
2. By mechanize operation, reduce intensity of labour of stoker.
3. Easy for installation, when on site, only install slag remover, valve, pipe, water and power, etc., the boiler can be launched into running, additionally, the firing is fast.
4. Easy for installation and moving, save a great amount of capital outlay.
5. Fule: Biomass, coal, wood, rice husk, shells, pellets, bagasse, waste , lower calorific value: 12792KJ/Kg.

xiangqingpic

Parameter :

DZG(L)Horizontal Type Coal-Burning Steam Boiler

Main Technology Parameter List

Model  DZG1-0.7-A II
DZG1-1.0-A II
DZG1-1.25-A II
DZG2-1.0-A II
DZG2-1.25-A II
DZG2-1.57-AII
DZG4-1.25-A II
DZG4-1.57-A II 
DZL1-0.7-A II
DZL1-1.0- A II
DZL1-1.25- A II
DZL1-1.57- A II
DZL1-2.45- A II
Rated Capacity T/h 1 2 4 1
Rated Working Pressure Mpa 0.7/1.0/1.25 1.0/1.25/1.57 1.25/1.57 0.7/1.0/1.25/1.57/2.45
Rated Steam Temp. 170/183/194 183/194/204 194/204 170/183/194/204/226
Feed Water Temp. 20 20 20 20
Fuel Consumption  Kg/H 170 330 600 170
Thermal Efficiency  % 77 77 78 78
Heating Surface m² Boiler Body 32.4 33.85 75.75 32.4
Economizer 12.51 24.64 38.5 12.51
Grate area   m² 1.37 2.3 2.05
Designed Fuel  Type Bituminous Coal Bituminous Coal Bituminous Coal Bituminous Coal
Max. Transport Weight  T 10.6 19.6 26.5 13.3
Max. Transport Dimension  m 4.75×2.1×2.6 5.7×3.4×4.6 5.49×2.6×3.5 5.65×2.1×2.6
Boiler Auxiliary Equipment Model and Specification
Air Blower Model T4-72-11;3.2A;Right225° T4-72-11;3.2A;Righ 315° T4-72-11;4A; Right 315° T4-72-11;3.2A; Right 225°
Motor Power N=1.5 Kw N=3 Kw N=5.5 Kw N=1.5 Kw
Draft Fan Model YX9-35-11;5C ; Right 0° Y-9-26;6.3C ; Right 0° Y-9-26;9D;Right 0° YX 9-35-11;5C; Right 0°
Motor Power N=5.5 Kw N=11 Kw N=22 Kw N=5.5 Kw
Gear Box Model GL-5P
Motor Power N=0.55 Kw
Feed Water Pump Model 1.5WCT-120 1½ GC5x7 1½ GC5x7 1.5WCT-120
Motor Power N=2.2 Kw N=7.5 Kw N=7.5 Kw N=2.2 Kw
Dust Remover Model XD-1 XD-2 XD-4 XD-1

 

Model DZL2-1.0-AII
DZL2-1.25-AII
DZL2-1.57-AII
DZL2-2.45-AII   
DZL4-1.25-AII
DZL4-1.57-AII
DZL4-2.45-AII 
DZL6-1.25-AII
DZL6-1.57-AII
DZL6-2.45-AII 
DZL8-1.57-AII DZL10-1.25-AII
DZL10-1.57-AII
DZL10-2.45-AII
Rated Capacity T/h 2 4 6 8 10
Rated Working Pressure Mpa 1.0/1.25/1.57/2.45 1.25/1.57/2.45 1.25/1.57/2.45 1.57 1.25/1.57/2.45
Rated Steam Temp. 183/194/204/226 194/204/226 194/204/226 203.04 194/204/226
Feed Water Temp. 20 20 20/60 20 20/60
Fuel Consumption  Kg/H ~310 ~590 ~900 ~1200 ~1440
Thermal Efficiency  % 78 80 77.44 78 80.6
Heating Surface m² Boiler Body 33.85 75.75 142 205 347
Economizer 24.64 38.5 87.2 139.52
Grate area   m² 3.5 4.66 7.4 8.4 10.98
Designed Fuel Type Bituminous Coal Bituminous Coal Bituminous Coal Bituminous Coal
Max.Transport Weight  Ton 21 26.5 38 33 28/29
Max. Transport Dimension  m 5.9×2.2×3.3 6.5×2.6×3.524 7.4×3.2×4.2 8.1×3.2×4.2 7.6×3.2×3.5
Boiler Auxiliary Equipment Model and Specification
Air Blower Model T4-72-11;3.2A;Right315° T4-72-11;4A;Righ 315° T4-72-11;5A; Right 225° GG8-Na;7.1A; Right 225° 10TG811DRight 225°
Motor Power N=3 Kw N=5.5 Kw N=11 Kw N=11 Kw N=15 Kw
Draft Fan Model Y9-26;6.3C; Right 0° Y-9-26;9D; Right 0° Y-8-39;9D;Right 0° GY8-1;Na9.5D;Right 0° 10JY;9.5D; Right 0°
Motor Power N=11 Kw N=22 Kw N=30Kw N=37Kw N=45 Kw
Gear Box Model GL-5P GL-5P GL-10P GL-16P
Motor Power N=0.55 Kw N=0.55 Kw N=1.1 Kw N=1.1 Kw
Feed Water Pump Model 1½ GC 5×7 1½ GC 5×7 DG 6-25×7 2GC-5xT 1½ GC 6×6
Motor Power N=7.5 Kw N=7.5 Kw N=7.5 Kw N=22 Kw N=2.2 Kw
Dust Remover Model XD-2 XD-4 XD-6 XD-8 XD-10

Product detail pictures:

Hot-selling Industrial Electric Boiler - Single Drum Steam Boiler – Double Rings detail pictures


Related Product Guide:
Boiler Structure

We love an incredibly fantastic standing amid our consumers for our superb item high quality, aggressive rate and also the finest assistance for Hot-selling Industrial Electric Boiler - Single Drum Steam Boiler – Double Rings , The product will supply to all over the world, such as: Portugal, Chile, Sevilla, They are sturdy modeling and promoting effectively all over the world. Never ever disappearing major functions within a quick time, it's a have to for you of fantastic good quality. Guided by the principle of Prudence, Efficiency, Union and Innovation. the corporation. ake an excellent efforts to expand its international trade, raise its organization. rofit and raise its export scale. We are confident that we are going to have a bright prospect and to be distributed all over the world in the years to come.
  • The customer service staff's attitude is very sincere and the reply is timely and very detailed, this is very helpful for our deal,thank you.
    5 Stars By Margaret from Vancouver - 2017.11.20 15:58
    Adhering to the business principle of mutual benefits, we have a happy and successful transaction, we think we will be the best business partner.
    5 Stars By Lena from Lebanon - 2017.07.28 15:46
    Write your message here and send it to us

    Related products

    • Leading Manufacturer for Biomass Heating - Boiler Water Treatment – Double Rings

      Leading Manufacturer for Biomass Heating - Boi...

      More photos 1. Quartz sand filter — mainly used for the removal of sediment from water. 2. Active Carbon filter– mainly used for chlorine removal and other organic gases and to clear up the taste of water . 3. Water Softener– exchange “ions” of calcium and magnesium with the most common and easiest method. 4. Precision filter– mainly used for removing microorganisms,chlorine,part of the heavy metal ions more precisely 5. High pressure pump– Provi...

    • Hot-selling Industrial Electric Boiler - DHL Corner Tube Bulk Water Pipe Boiler – Double Rings

      Hot-selling Industrial Electric Boiler - DHL C...

      Introduction: As a new type of mature high-performance with low-pollution clean coal technology. circulating fluidized bed combustion(CFBC)technology is unlike others that it has a lot of unique characteristics. 1. Circulating fluidized bed is of low-temperature combustion, therefore nitrogen oxides emissions of such boiler is much lower than that of coal-powder boiler, and such boiler could directly desulfurize during combustion process. Circulating fluidized bed boiler with high desulfuriza...

    • Factory wholesale Oil Condensing Boilers - Boiler Ladder and Stair – Double Rings

      Factory wholesale Oil Condensing Boilers - Boi...

      Quality Control 1 Strength Calculation Report for Applied Materials after Inspection Machine inspected. 2 100%NDT(non-destructive inspection) report of steel plate,tube and welding rod; 3 100% X-ray inspection report (welding seam):to ensure the quality of the entire boiler; 4 Hydraulic test report:ensure the standard working pressure and safety; 5 Third-party inspection report:by Special Equipment Safety Supervision Inspection Institute of Jiang Su Province 6 Manufacturer Produc...

    • Popular Design for Water Boilers - Single Drum Hot Water Boiler – Double Rings

      Popular Design for Water Boilers - Single Drum...

      Parameter : DZG(L)Bearing Pressure Hot water boiler Main Technology Parameter List Model DZG0.7-0.7/95/70 DZL0.7-0.7/95/70  DZG1.4-0.7/95/70 DZL1.4-0.7/95/70 DZL1.4-1.0/115/70 DZL28-1.0/115/70 DZL2.8-1.25/130/70 DZL4.2-1.0/115/70 DZL4.2-1.25/130/70 Rated Capacity T/h 0.7 1.4 2.8 4.2 Rated Working Pressure Mpa 0.7 0.7/1.0 1.0/1.25 1.0/1.25 Rated Steam Temp. ℃ 95 95/115 115/130 115/130 Feed Water Temp. ℃ 70 70 70 70 Fuel Consumption  Kg/H ~150 ~310 ~590 ~900 Thermal Efficiency ...

    • Free sample for Stoker Boiler - Boiler Ladder and Stair – Double Rings

      Free sample for Stoker Boiler - Boiler Ladder ...

      Quality Control 1 Strength Calculation Report for Applied Materials after Inspection Machine inspected. 2 100%NDT(non-destructive inspection) report of steel plate,tube and welding rod; 3 100% X-ray inspection report (welding seam):to ensure the quality of the entire boiler; 4 Hydraulic test report:ensure the standard working pressure and safety; 5 Third-party inspection report:by Special Equipment Safety Supervision Inspection Institute of Jiang Su Province 6 Manufacturer Produc...

    • OEM Customized China Gas Boiler - Gas Oil Thermal Oil Boiler – Double Rings

      OEM Customized China Gas Boiler - Gas Oil Ther...

      Introduction The gas-fired Thermol Oil Boiler uses a closed cycle for heat supply and liquid phase transport of heat energy, which has the characteristics of less heat loss, and effectively prolongs the life of the boiler, energy saving and environmental protection. The inside of the furnace adopts a three-circuit tube design and a direct flow structure to ensure the safety of the boiler and effectively extend the service life of the boiler. The coil structure increases the heating surf...